Whether you are in the market for NSN parts, military and defense parts, aerospace parts, or other similar product solutions, Buy Military Fasteners is your one-stop shop with an expansive selection tracing back to premier manufacturers and entities that we trust. Thank you for taking an interest in part number CM-21A, a 3M Company item that is listed alongside the description “Alarm Gas Automatic” and the NSN 6665015302725. As part number CM-21A is ready for purchase on our website at any time, you are invited to fill out and submit the RFQ form provided on this page for the means of requesting a quote for your comparisons. All that we ask is that you supply us with crucial details such as your target price and expected shipping time frame, that way we can best customize a solution that caters to your unique requirements and constraints alike.
Note : We Will Not Share Your Information To Any Third Parties.
As customers explore our vast selection, they can take advantage of services like our CAGE Code search features or database filters to quickly locate products of interest for purchase. For example, part number CM-21A is listed alongside the NSN 6665-01-530-2725, meaning that it also belongs to FSC 6665 Hazard Detecting Instruments And Apparatus. With this in mind, kick off procurement with us today with assurance that we can even fulfill your most difficult needs.
MRC | Criteria | Characteristic |
---|---|---|
APGF | DESIGN TYPE | NONTRIPOD MOUNTING |
AFJK | III CUBIC MEASURE | 38.250 CUBIC INCHES |
SUPP | III SUPPLEMENTARY FEATURES | DIMENTIONS ARE 4.5 X 4 X 2.125 INCHES. ITEM SHOULD BE MOUNTED 4 TO 5 FEET ABOVE FLOOR LEVEL. |
FEAT | SPECIAL FEATURES | CM-21A ACTIVATES FAN RELAY AT 35 PPM OF CO AVERAGED OVER 5 MINUTES. (25 PPM IS SELECTABLE) ALARM RELAY WILL BE ACTIVATED AT 100 PPM OF CO AFTER 30 MINTUTES OR 200 PPM AFTER 10 MINUTES. 5 AMP SPDT FAN RELAY CONTROLS STARTERS OF EXHAUST FANS. A 0.5 AMP N.O. ALARM RELAY CONNECTS TO WARNING DEVICES OR CONTROL PANELS. |
BRQN | MEDIA DETECTED | CARBON MONOXIDE |
CXCY | III PART NAME ASSIGNED BY CONTROLLING AGENCY | CARBON MONOXIDE DETECTOR AND CONTROLLER |
ALBY | USAGE DESIGN | INDUSTRIAL |
ALXZ | SPECIFIC USAGE DESIGN | DESIGNED FOR CO DETECTION AND AUTOMATED EXHAUST FAN CONTROL IN AUTOMOTIVE MAINTENANCE FACILITES, ENCLOSED PARKING GARAGES, WAREHOUSES WITH FORKLIFTS, ETC. |
AMKD | INDICATOR TYPE | RED LIGHT AND HORN |