Whether you are in the market for NSN parts, military and defense parts, aerospace parts, or other similar product solutions, Buy Military Fasteners is your one-stop shop with an expansive selection tracing back to premier manufacturers and entities that we trust. Thank you for taking an interest in part number HE2-A3-5-2, a Eaton Corporation item that is listed alongside the description “Circuit Breaker” and the NSN 5925010733682. As part number HE2-A3-5-2 is ready for purchase on our website at any time, you are invited to fill out and submit the RFQ form provided on this page for the means of requesting a quote for your comparisons. All that we ask is that you supply us with crucial details such as your target price and expected shipping time frame, that way we can best customize a solution that caters to your unique requirements and constraints alike.
Note : We Will Not Share Your Information To Any Third Parties.
As customers explore our vast selection, they can take advantage of services like our CAGE Code search features or database filters to quickly locate products of interest for purchase. For example, part number HE2-A3-5-2 is listed alongside the NSN 5925-01-073-3682, meaning that it also belongs to FSC 5925 Circuit Breakers. With this in mind, kick off procurement with us today with assurance that we can even fulfill your most difficult needs.
NSN | FSC | NIIN | CLS | Hazmat | DEMIL | Cancelled NSN |
---|---|---|---|---|---|---|
5925-01-073-3682 Item Description: CIRCUIT BREAKER | 5925 | 010733682 | P | |||
CIIC | HCC | ESD | PMIC | Criticality | ENAC | |
Part Number | ISC | RNVC | RNCC | HCC | MSDS | SADC |
HE2-A3-5-2 | 5 | 9 | 3 |
MRC | Criteria | Characteristic |
---|---|---|
CPLM | Maximum Continuous Load Current Rating Per Pole | 5.0 AMPERES AC ALL LOCATIONS |
ABXD | Bushing Length | 0.375 INCHES NOMINAL |
CPRF | Operating Voltage Type And Rating Per Pole In Volts | 250.0 AC ALL LOCATIONS |
CPRH | Circuit Protection Type | OVERCURRENT ALL LOCATIONS |
CPRJ | Trip Release Method | MAGNETIC-HYDRAULIC ALL LOCATIONS |
AXHR | Mounting Facility Type And Quantity | THD BUSHING W/PANEL SEAL |
AKPX | Pole Quantity | 2 |
CPRN | Ultimate Trip Rating Of Continuous Current Rating Per Pole In Percent | 125.0 ALL LOCATIONS |
FREQ | Frequency In Hertz | 60.0 ALL LOCATIONS |
CPRL | Trip Release Characteristic | TIME DELAY ALL LOCATIONS |
CPRR | Main Contact Tripping Mechanism Type | TRIP FREE |
ADAT | Body Width | 1.281 INCHES MAXIMUM |
MRC | Decoded Requirement | Clear Text Reply |
CPRX | Actuator Position Designation | BETWEEN POLE ONE AND TWO |
CPRT | Manual Actuator Type And Quantity | 1 TOGGLE |
ADTV | Case Material | METAL |
CPRW | Actuator Function | TRIP-RESET |
THSD | Thread Series Designator | UNEF |
TTQY | Terminal Type And Quantity | 4 WIRE HOOK |
AJWX | Mounting Surface To Terminal End Distance | 1.700 INCHES MAXIMUM |
ADAQ | Body Length | 1.562 INCHES MAXIMUM |
CQJX | Nominal Thread Size | 0.375 INCHES |
FEAT | Special Features | HERMETICALLY SEALED CASE |
AEBP | Center To Center Distance Between Terminals Parallel To Length | 0.875 INCHES NOMINAL |
AAQL | Body Style | MULTIPOLE-SINGLE ACTUATOR TYPE |
AEBQ | Center To Center Distance Between Terminals Parallel To Width | 0.625 INCHES NOMINAL |
CPRG | Maximum Interrupting Capacity Current Type And Rating Per Pole In Amps | 300.0 AC ALL LOCATIONS |
CQWN | Trip Delay Time In Seconds Per Rated Continuous Current | 0.150 MINIMUM AT 200 PCT ALL LOCATIONS AND 0.700 MAXIMUM AT 200 PCT ALL LOCATIONS AND 0.007 MINIMUM AT 500 PCT ALL LOCATIONS AND 0.040 MAXIMUM AT 500 PCT ALL LOCATIONS |
CMLP | Thread Quantity Per Inch | 32 |
CPRQ | Reset Method | MANUAL |
CPSM | Internal Trip Release Configuration | SERIES TRIP ALL LOCATIONS |
CQXF | Inclosure Protection Type For Which Designed | FUNGUS RESISTANT AND MOISTURE RESISTANT |