Whether you are in the market for NSN parts, military and defense parts, aerospace parts, or other similar product solutions, Buy Military Fasteners is your one-stop shop with an expansive selection tracing back to premier manufacturers and entities that we trust. Thank you for taking an interest in part number 3XAM1516-20-416AC-1 400 HZ, a Heinemann Electric Co Inc item that is listed alongside the description “Circuit Breaker” and the NSN 5925008349372. As part number 3XAM1516-20-416AC-1 400 HZ is ready for purchase on our website at any time, you are invited to fill out and submit the RFQ form provided on this page for the means of requesting a quote for your comparisons. All that we ask is that you supply us with crucial details such as your target price and expected shipping time frame, that way we can best customize a solution that caters to your unique requirements and constraints alike.
Note : We Will Not Share Your Information To Any Third Parties.
As customers explore our vast selection, they can take advantage of services like our CAGE Code search features or database filters to quickly locate products of interest for purchase. For example, part number 3XAM1516-20-416AC-1 400 HZ is listed alongside the NSN 5925-00-834-9372, meaning that it also belongs to FSC 5925 Circuit Breakers. With this in mind, kick off procurement with us today with assurance that we can even fulfill your most difficult needs.
NSN | FSC | NIIN | CLS | Hazmat | DEMIL | Cancelled NSN |
---|---|---|---|---|---|---|
5925-00-834-9372 Item PartTypeName: CIRCUIT BREAKER | 5925 | 008349372 | P | |||
CIIC | HCC | ESD | PMIC | Criticality | ENAC | |
U | ||||||
Part Number | ISC | RNVC | RNCC | HCC | MSDS | SADC |
53-161-3-MG3 | 2 | 9 | 5 |
MRC | Criteria | Characteristic |
---|---|---|
AEBY | DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY LENGTH | 2.740 INCHES MINIMUM AND 2.760 INCHES MAXIMUM |
AFJN | FRAGILITY FACTOR | MODERATELY RUGGED |
AKPX | POLE QUANTITY | 3 |
BBRG | STORAGE TYPE | GENERAL PURPOSE WAREHOUSE |
CPLM | MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE | 20.0 AMPERES AC ALL LOCATIONS |
CPRG | MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS | 1500.0 AC ALL LOCATIONS |
CPRN | ULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT | 125.0 ALL LOCATIONS |
CPRR | MAIN CONTACT TRIPPING MECHANISM TYPE | TRIP FREE |
CPRT | MANUAL ACTUATOR TYPE AND QUANTITY | 3 TOGGLE |
CPRY | EXTERNAL ACTUATOR LINKAGE ARRANGEMENT | ONE,TWO,AND THREE LINKED |
CPSM | INTERNAL TRIP RELEASE CONFIGURATION | SERIES TRIP ALL LOCATIONS |
CQJX | NOMINAL THREAD SIZE | 0.138 INCHES |
CQWN | TRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENT | 4.000 MINIMUM AT 200 PCT AND 10.000 MAXIMUM AT 200 PCT ALL LOCATIONS |
CQXF | INCLOSURE PROTECTION TYPE FOR WHICH DESIGNED | DUSTPROOF AND FUNGUS PROOF |
CWJK | CASE MATERIAL | PLASTIC |
TTQY | TERMINAL TYPE AND QUANTITY | 6 THREADED STUD |
AAQL | BODY STYLE | MULTIPOLE-MULTIPLE ACTUATOR TYPE |
ADAQ | BODY LENGTH | 3.709 INCHES MINIMUM AND 3.729 INCHES MAXIMUM |
ADAT | BODY WIDTH | 3.042 INCHES MINIMUM AND 3.062 INCHES MAXIMUM |
AEBP | CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO LENGTH | 3.053 INCHES MINIMUM AND 3.073 INCHES MAXIMUM |
AEBQ | CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO WIDTH | 1.021 INCHES MINIMUM AND 1.041 INCHES MAXIMUM |
AEHA | DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY WIDTH | 1.021 INCHES MINIMUM AND 1.041 INCHES MAXIMUM |
AJEC | BOSS HEIGHT | 0.146 INCHES MINIMUM AND 0.166 INCHES MAXIMUM |
AJWX | MOUNTING SURFACE TO TERMINAL END DISTANCE | 3.239 INCHES NOMINAL |
APNQ | ARC QUENCHING METHOD | MAGNETIC BLOWOUT |
AXHR | MOUNTING FACILITY TYPE AND QUANTITY | 6 THREADED HOLE |
BBRJ | SPECIAL HANDLING FEATURE | MAGNETIC |
CMLP | THREAD QUANTITY PER INCH | 32 |
CPRF | OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS | 250.0 AC ALL LOCATIONS |
CPRH | CIRCUIT PROTECTION TYPE | OVERCURRENT ALL LOCATIONS |
CPRJ | TRIP RELEASE METHOD | MAGNETIC-HYDRAULIC ALL LOCATIONS |
CPRL | TRIP RELEASE CHARACTERISTIC | TIME DELAY ALL LOCATIONS |
CPRQ | RESET METHOD | MANUAL |
CPRW | ACTUATOR FUNCTION | TRIP-RESET |
CPRX | ACTUATOR POSITION DESIGNATION | AT EACH POLE |
FREQ | FREQUENCY IN HERTZ | 60.0 ALL LOCATIONS |
THSD | THREAD SERIES DESIGNATOR | UNC |